A Mitsubishi Electric Mr Slim in Edmondson Park kept losing gas. The leak was in the pair coil between the units.
Gas Leak in the Pipework: A Real Mitsubishi Electric Job
What A Pair Coil Is, And Why It Leaks
The pair coil is the insulated copper pipework that runs between the indoor and outdoor units. One pipe carries liquid refrigerant, the other carries gas back. It's usually hidden in walls, ceilings and under the floor.
Leaks in the pair coil happen at joints, at kinks from the install, or from damage like a screw through the wall. When the leak is inside the pipe itself and it's hidden in the building, it usually can't be repaired where it is, so the pipe gets replaced.
How we find a pipework leak, step by step
- Sweep the accessible joints and components with an electronic leak detector.
- Pressure test the whole system with nitrogen and a tracer gas.
- Isolate the indoor unit, outdoor unit and pair coil to work out which part is losing pressure.
- Confirm the leak location, then work out whether it can be reached and repaired.
- Quote the fix: new pair coil, pressure test, evacuate, regas and test.
What not to do
- Don't keep topping it up. The gas will keep escaping.
- Don't run a system that's low on gas. It can damage the compressor.
- Don't patch a leak you can't properly get to. It'll fail again.
The Job
- Suburb: Edmondson Park
- Job: Refrigerant leak find
- System: Mitsubishi Electric Mr Slim 14kW, R32, built 2022
The system kept losing refrigerant. The customer wanted it found, not just topped up.
What We Found
We pressurised the system with nitrogen and a trace gas and tracked it down to the liquid line of the pair coil. That's not a fitting that can be tightened. The leak is in the coil itself, so it can't be fixed in place.
The readings
- Pressure test logged on our digital gauges (graph below)
What We Did And Recommended
Our quote covered replacing the pair coil, then pressure testing, evacuating and regassing the system so it's sealed properly.
Topping up a system with a known leak just wastes the gas and your money.
More on Mitsubishi Electric repairs, regas costs and rules, and air conditioning in Edmondson Park.
FAQ
Common Questions
It’s the insulated pair of copper pipes connecting the indoor and outdoor units. One carries liquid refrigerant, the other carries gas back to the outdoor unit.
If the leak is at a joint we can reach, often yes. If it’s inside the pipe and hidden in the building, like this job, the pair coil is replaced.
We pressure test with nitrogen and tracer gas and isolate each part. The section that loses pressure is where the leak is.
The new pipework is pressure tested with nitrogen to prove it’s sealed, then the system is evacuated, regassed and tested.