An Alinta Energy geothermal system lost all its gas. We found the leak in a badly corroded indoor coil, and pointed them at the warranty.
Corroded Indoor Coil on a Geothermal System: Edmondson Park
Why Indoor Coils Corrode And Leak
The indoor coil is where the cooling happens. It's thin copper tubing with fins, and it's wet with condensation every time the system cools. Over time, corrosion can eat through the tubing and let the refrigerant out.
Some corrosion is normal on an old system. On a system only a few years old, a coil corroding through isn't normal wear and tear, and it's worth asking the manufacturer about warranty before you pay for anything.
How we find a coil leak, step by step
- Confirm the system has lost refrigerant. This one had no gas left at all.
- Split the system and pressure test each side on its own. Here, the geothermal side held.
- Confirm the leak is in the indoor coil and inspect how far the corrosion has gone.
- Work out access. In a tight roof, getting the coil out can mean opening the ceiling.
- Check the build date and occupancy date against the warranty.
- Give the options straight: replace the coil, or chase the warranty first.
What not to do
- Don't patch a badly corroded coil. It'll start leaking somewhere else.
- Don't pay for a repair before you've checked the warranty on a newer system.
- Don't keep regassing it. You'll pay for refrigerant every time.
See regas costs and rules and how long air conditioners last.
The Job
- Suburb: Edmondson Park
- Job: Refrigerant leak find
- System: Alinta Energy Geothermal GEO36BS, R410A, built 2020
The system was showing an E9 code and not running properly. It's a geothermal system, which you don't see often.
What We Found
The system had lost its entire charge. To find where, we split it and pressure tested the geothermal side and the indoor side separately. The geothermal side held.
The leak is in the indoor coil, and the coil is badly corroded. The original install test pressures were still written on the unit, which helped.
The readings
- Split pressure test: geothermal side held, indoor side leaking
What We Did And Recommended
The system was built in 2020 and the home was first lived in in 2021, so it may still be under warranty. Our advice was to chase that first.
Swapping the coil means opening up the ceiling. Patching a coil this corroded isn't worth it, because it'll just leak somewhere else.
More on regas costs and rules, E-codes and error codes, and air conditioning in Edmondson Park.
FAQ
Common Questions
The coil is wet with condensation every time it cools, and over years that can cause corrosion. On a system only a few years old, early corrosion isn’t normal and is worth raising with the manufacturer.
It can be tried, but we don’t recommend it on a badly corroded coil. A patch is unlikely to last, and it’ll probably leak again somewhere else.
It depends on the manufacturer and the system’s age. This one was built in 2020 and the home was first lived in in 2021, so we suggested chasing the warranty first.
On this system, E9 pointed to low pressure, and it had lost its full charge. Our Actron error codes guide covers E9 on Actron controllers.
Get A Report Like This For Your System
Every Standard Service ($250+GST, $110+GST for each extra unit) comes with a written report like this one, with readings and photos, emailed to you the same day. Diagnostics are $250+GST and come with a written report too.
Give us a call on (02) 9820 4500 or book online. Our own crew, not subbies. NSW contractor licence 273312C, ARCtick AU13058. Servicing Sydney since 1991.