A pre-summer service on a 2015 Daikin ducted picked up a unit working harder than it should.
High Head Pressure Explained: A Daikin Service in Ingleburn
What High Head Pressure Means
Head pressure is the pressure on the high side of the system, where the outdoor unit gets rid of heat. When it runs higher than it should for the conditions, the compressor is working harder to push against it.
Common causes are a dirty or blocked outdoor coil, poor airflow around the outdoor unit, a weak fan, or too much refrigerant. Higher head pressure means more wear on the compressor and higher running costs, and on an older unit that's what shortens its life.
How we check it, step by step
- Run the system under load and let it settle.
- Read the suction and discharge pressures and convert them to saturation temperatures.
- Measure the liquid line temperature and work out subcooling.
- Check compressor current against the rated maximum.
- Look at the outdoor coil, fan and the space around the unit.
- Compare it all against what's normal for the day's conditions.
What not to do
- Don't let plants, fences or stored junk crowd the outdoor unit.
- Don't hose the outdoor coil with high pressure. It flattens the fins.
- Don't add gas without readings. Overcharging raises head pressure too.
The Job
- Suburb: Ingleburn
- Job: General service before summer
- System: Daikin ducted (RZQ140LV1), R410A, built 2015
- Price: $250+GST
A service to get the system ready for summer.
What We Found
The head pressure, on the high side of the system, was higher than it should be for the conditions on the day. A compressor working against high pressure runs hotter and harder, and on an 11-year-old unit that shortens its life.
The return filter was dirty as well.
The readings
- Suction 969 kPa, discharge 3,115 kPa
- Saturation temperatures 9.5 and 52 degrees, liquid line 39
- Subcooling 13K
- Compressor 16.5A, against 28.1A maximum
What We Did And Recommended
Filters, drain and coils were all done, and the high head pressure is flagged in the report so it gets checked again.
More on how often to service your air con, Daikin repairs, and air conditioning in Ingleburn.
FAQ
Common Questions
It’s the pressure on the high side of the system, where the outdoor unit gets rid of heat.
Usually a dirty outdoor coil, poor airflow around the outdoor unit, a weak fan, or too much refrigerant.
Over time, yes. The compressor works harder, running costs go up, and on an older unit it shortens its life.
Suction and discharge pressures, saturation temperatures, liquid line temperature, subcooling and compressor current, all written up in the report.
Get A Report Like This For Your System
Every Standard Service ($250+GST, $110+GST for each extra unit) comes with a written report like this one, with readings and photos, emailed to you the same day. Diagnostics are $250+GST and come with a written report too.