An ActronAir ducted with one zone stuck. The zone motor wiring had worked loose along the duct.
Why a Ducted Zone Stops Working: A Real Bardia Job
Why A Ducted Zone Stops Working
Each zone on a ducted system is controlled by a damper with a small motor, wired back to the zone controller. When a zone stops responding, it's usually the motor, the wiring to it, or the controller.
Wiring is easy to miss. Cables run along ductwork in the roof and can work loose over time, especially if the ducts move when the system starts and stops.
How we trace it, step by step
- Test every zone from the controller and note which won't open or close.
- Follow the wiring from the controller to the zone motor in the roof.
- Check the connection at the motor and along the duct run.
- Repair and secure the wiring so it can't work loose again.
- Test the zone through the controller and watch the system pressures rise as the zone comes back online.
What not to do
- Don't climb into the roof and pull at wires. There's live wiring up there.
- Don't assume the motor's dead before checking the wiring.
- Don't run with a zone stuck shut for long if it's meant to be open.
See ducted repairs and Actron repairs.
The Job
- Suburb: Bardia
- Job: Ducted repair and service
- System: ActronAir 12.4kW ducted, R410A
The customer had performance concerns and a duct to reconnect, and we serviced the system while we were there.
What We Found
One zone wasn't doing anything. The wiring to its zone motor had worked loose along the duct, so the controller couldn't open or close that zone at all.
The readings
- Suction 834 kPa, discharge 3,385 kPa
- Compressor 4.11 / 3.50 / 3.72 amps, against 9.5A rated
- Indoor fan 3.51A
What We Did And Recommended
We repaired the wiring, taped and secured it so it can't work loose again, and tested every zone through the controller.
More on ducted repairs, Actron repairs, and our Edmondson Park air conditioning page, which covers Bardia.
FAQ
Common Questions
Usually the zone motor, its wiring, or the controller. On this Bardia job, the wiring had worked loose along the duct.
We test it through the controller, and we watch the pressures. When a closed zone opens, the system picks up load and the pressures rise. The logged trace shows the step up.
That’s normal. With a zone shut, the system sees less load. Once the zone opens and air flows across the coil, the pressures lift to where they should be.
Not always. Check the wiring first. If the motor is dead, it’s a small part to replace.