A 2022 Daikin 22kW with good gas and good electrics that still wasn't cooling. The answer was the return air.
Why a New Ducted System Won't Cool: Edmondson Park
Why Return Air Matters On A Ducted System
A ducted system can only cool as much air as it can pull back in. The return air grille and ducting feed the indoor unit. If they're too small or a duct collapses, the coil gets starved of air, runs too cold, and the house never quite cools.
The tell-tale sign is in the readings. Gas and electrics look fine, but the suction pressure sits low, which puts the coil well below zero on a mild day.
How we find it, step by step
- Check standing pressure to confirm the gas charge.
- Measure compressor and fan current against the unit's ratings.
- Run it in cooling for 30 minutes and watch the suction pressure and coil temperature.
- If the coil's too cold, go into the roof and follow the return air duct.
- Measure the return grille and ducts against the system size.
What not to do
- Don't add gas to a system with the right charge. It won't fix an airflow problem.
- Don't replace a young system that isn't the problem.
- Don't block or cover the return air grille.
See ducted repairs and air con not cooling.
The Job
- Suburb: Edmondson Park
- Job: General service, not cooling well
- System: Daikin 22kW ducted (RZYQ8TY1), R410A, built 2022
- Price: $250+GST
The customer booked a service because the system wasn't cooling the way it used to. At four years old, it shouldn't be struggling.
What We Found
The gas charge and electrics were fine. But after 30 minutes in cooling, suction settled at around 635 kPa, which puts the indoor coil at about minus 2.5 degrees. On a mild day that's too cold, and it means the coil isn't getting enough air across it.
In the roof, the return air duct had collapsed where it runs against the steel ceiling framing, choking off the air back to the unit. The return grille is also undersized: a 900 x 500 grille feeding two 400 mm ducts isn't enough for a 22kW system.
The readings
- Standing pressure 1,339 kPa at 20 degrees
- Indoor fan 2.05A
- Compressor 10.74 / 11.05 / 11.24 amps, against 16.1A maximum
- Suction about 635 kPa, coil about minus 2.5 degrees
What We Did And Recommended
We quoted replacing the collapsed duct and supporting it properly, with an option to upsize the return air while we're up there.
A gas top-up or a new unit wouldn't have fixed this one.
This report also appears on our main service reports page. More on ducted repairs and air conditioning in Edmondson Park.
FAQ
Common Questions
If the gas and electrics are fine, look at airflow. A collapsed return duct or an undersized return grille will starve the coil of air.
It’s the air pulled back from the house into the indoor unit through the return grille and duct. The system cools that air and sends it back out.
It depends on the system size. On this 22kW system, a 900 x 500 grille feeding two 400 mm ducts was too small.
Yes. The collapsed section is replaced and supported properly so it can’t be crushed again.