Ducted Running But Not Cooling: A Real Spring Farm Job

A Fujitsu ducted that ran but wouldn't cool. The coil had iced up. The cause was the filters.

Ducted Running But Not Cooling: A Real Spring Farm Job

Why A Ducted System Runs But Doesn't Cool

If your ducted is running, fans going, but the house isn't getting cool, the most common cause is airflow. The system needs a lot of air moving across the indoor coil. When the filters clog, the coil runs too cold, ice builds up, and the system starts winding itself back to protect itself.

Other causes are low gas, a collapsed or disconnected duct, a faulty zone motor, or a dirty outdoor coil. Each one looks the same from inside the house, which is why it's worth testing rather than guessing.

What we check, step by step

  1. The return air filters. Clogged filters are the number one cause.
  2. Ice on the pipework at the outdoor unit, a sign the coil is running too cold.
  3. Refrigerant pressures and temperatures with digital gauges.
  4. Air temperature coming out of the vents against the room temperature.
  5. The ducts and zones in the roof.
  6. How the indoor unit is hung and running.

What not to do

  • Don't turn the temperature right down to force it. That makes icing worse.
  • Don't keep running it if you can see ice. Turn it off and let it thaw.
  • Don't let anyone add gas before they've checked the filters and airflow.

See air con not cooling and ice on your air con.

The Job

  • Suburb: Spring Farm
  • Job: Repair call, system not cooling
  • System: Fujitsu 12.5kW ducted, R410A
  • Price: $250+GST diagnostic fee

The ducted system wasn't cooling the house, and the customer was bracing for a big repair.

What We Found

Both return air filters were choked. With so little air getting through, the coil ran so cold it iced up the pipework, and the unit kept winding itself back to protect itself.

We also noticed the indoor unit had been hung on a slant when it was first installed, and it wobbles.

The readings

  • After the fix: supply air 14 degrees with the room at 24 and 20 outside
  • Gas charge slightly lean, no gas added
Dirty ducted air conditioner filters next to clean ones
Choked filters next to clean ones.
Fujitsu ducted indoor unit and ducting in a roof space
The indoor unit in the roof.

What We Did And Recommended

We cleaned the filters, retested, and the system came good. No parts, no gas.

Our advice: clean the filters every three months, budget for an indoor fan down the track, and we offered to quote on rehanging the indoor unit properly.

If your ducted isn't cooling, check the filters before you panic. More on that in air con not cooling and ice on your air con. We cover Spring Farm from our Camden air conditioning page.

Jay's Air Conditioning white icon logo showing the flame and tick brand symbol on a light grey background

FAQ

Common Questions

FAQ

Most often it’s clogged return air filters starving the coil of air. Other causes are low gas, a collapsed duct, a faulty zone or a dirty outdoor coil.

Yes. On this Spring Farm job, choked filters made the coil so cold it iced up and the system kept winding itself back. A filter clean fixed it.

Every three months, or more often over summer when it’s working hardest.

It depends on the conditions, but on this job, with the room at 24 and 20 outside, the vents settled around 14 degrees once the filters were clean.

Get A Report Like This For Your System

Every Standard Service ($250+GST, $110+GST for each extra unit) comes with a written report like this one, with readings and photos, emailed to you the same day. Diagnostics are $250+GST and come with a written report too.