Uneven airflow on a Fujitsu ducted, traced to one dead zone motor and a clogged filter.
Why Some Rooms Get No Air: A Real Rosemeadow Job
Why Some Rooms Get No Air
On a zoned ducted system, each zone has a damper in the duct that opens and closes, driven by a small zone motor. If a motor fails, that zone can stay shut no matter what the controller says.
Other causes of uneven airflow are a duct that's come off in the roof, dampers left half closed, a clogged return filter, or a room that just needs more air than one outlet can give it.
How we trace it, step by step
- Test each zone from the controller and see which ones respond.
- Check the zone motors and their wiring in the roof.
- Look for disconnected or crushed ducts.
- Check the return filter, since a blocked filter cuts air to every room.
- Run the system and watch the pressures to make sure the unit itself is healthy.
What not to do
- Don't close lots of zones to push air to one room. It strains the system.
- Don't ignore a zone that won't open. The system's still working hard for air that isn't getting there.
- Don't leave filters for a year. Clean them every one to three months.
See ducted repairs and Fujitsu repairs.
The Job
- Suburb: Rosemeadow
- Job: Ducted service, airflow complaint
- System: Fujitsu 12.5kW ducted, R410A
- Price: $250+GST
Some rooms were getting plenty of air and others weren't.
What We Found
The living room zone motor was dead. That's the motor that opens and closes the damper for that zone, so the controller could say the zone was on while the damper stayed shut.
The return filter was also very clogged, which cuts airflow to every room.
The readings
- Pressures watched over about 30 minutes: system performing as designed
- Compressor: 15.17A
What We Did And Recommended
We cleaned the filter and sent a quote for the zone motor. Our advice was to clean the filters every one to three months.
The system itself was fine. It just needed one part and a clean filter.
More on ducted repairs, Fujitsu repairs, and our Campbelltown air conditioning page, which covers Rosemeadow.
FAQ
Common Questions
Often a failed zone motor, a disconnected duct, or a damper that’s shut. A blocked return filter can also reduce airflow everywhere.
A small motor that opens and closes the damper for a zone. If it fails, that zone stays shut or stuck open.
It’s a fairly small part. We quote it once we’ve confirmed which motor has failed.
Every one to three months depending on use, plus a service once a year.