Servicing Older R22 Systems: Two Daikin Ducted in Mount Annan

Two older R22 Daikin ducted systems, a broken filter, a leaking Schrader valve, and a plan for what comes next.

Servicing Older R22 Systems: Two Daikin Ducted in Mount Annan

What To Know If Your System Runs On R22

R22 is the refrigerant older systems were built for. It's no longer made, so refrigerant and parts are getting harder and dearer to find. These systems can keep running well with servicing, but repairs get expensive, and it pays to plan ahead.

Older systems also lack some of the smarts of newer ones. This 20kW outdoor unit can't change its fan speed for mild weather, so on cooler days it can run out of balance and trip out.

What we check on an older system, step by step

  1. Clean the filters and check they're intact. A broken filter lets dust straight onto the coil.
  2. Run each system for 20 to 25 minutes and take full readings: pressures, superheat, subcooling and amps on each phase.
  3. Leak test service valves and Schrader cores.
  4. Inspect the outdoor coil for damage.
  5. Note what parts are still available.
  6. Give a plan: what to fix now, what to watch, and when replacing makes more sense.

What not to do

  • Don't pour big money into a major repair on an old R22 system without a replacement price to compare.
  • Don't run two systems against each other, one heating and one cooling, with returns close together.
  • Don't run it with a broken filter. It leads to dirty coils and drain leaks.

See repair or replace and Daikin repairs.

The Job

  • Suburb: Mount Annan
  • Job: Annual service on two ducted systems
  • Systems: Daikin 20kW ducted (3 phase) and Daikin 16kW ducted, both R22
  • Price: $250+GST

The customer booked their annual service on two older Daikin ducted systems. Both run on R22, the old refrigerant that's no longer made in Australia, so keeping them healthy matters more each year.

What We Found

The 20kW system's filter had split into two pieces. Dust was getting straight past it and onto the coil. A dirty coil holds water, and that ties back to the drain leak the customer had last year.

The suction Schrader valve was leaking, and the outdoor coil was damaged. On the 16kW system, superheat was running high, which can mean it's a touch low on gas.

The readings

  • 20kW in heating: low side 426 kPa, superheat 11.1K, high side 1,804 kPa, subcooling 7.4K
  • 20kW compressor: 11.08 / 10.58 / 10.32 amps across the three phases, indoor fan 4.15A
  • 16kW in cooling: low side 367 kPa, superheat about 17K, high side 1,262 kPa
  • 16kW compressor: 7.33 / 7.07 / 7.38 amps
Broken two-piece ducted air conditioner filters laid out on grass after removal
The 20kW filter, in two pieces.
Leak test spray on a Schrader valve on a Daikin ducted outdoor unit
Leak testing the suction Schrader valve.
Digital refrigerant readings and graph from a Daikin ducted air conditioner service
Live readings logged during the service.

What We Did And Recommended

Both filters were chemically cleaned. The Schrader valve was tightened and leak tested. Next visit, the filter and the valve core get replaced.

With R22 getting harder and dearer to source, our advice was to plan to replace the 20kW at its next major fault, not to pour money into it. And one more tip from the report: don't run one system on heat and the other on cool at the same time.

More on this: Daikin air conditioning repairs, repair or replace your air con, and our Mount Annan air conditioning page.

Jay's Air Conditioning white icon logo showing the flame and tick brand symbol on a light grey background

FAQ

Common Questions

FAQ

It’s no longer manufactured, so what’s left is getting scarcer and more expensive. That’s why repairs on R22 systems need careful thought.

Not necessarily. If it’s running well, servicing keeps it going. We’d suggest planning to replace it at the next major fault, rather than paying for a big repair.

Our Standard Service is $250+GST for the first unit and $110+GST for each extra unit.

Dust gets past it onto the coil and into the drain. That build-up can block the drain and cause leaks, which is what happened at this house the year before.

Get A Report Like This For Your System

Every Standard Service ($250+GST, $110+GST for each extra unit) comes with a written report like this one, with readings and photos, emailed to you the same day. Diagnostics are $250+GST and come with a written report too.

Give us a call on (02) 9820 4500 or book online. Our own crew, not subbies. NSW contractor licence 273312C, ARCtick AU13058. Servicing Sydney since 1991.

See all our service reports