An ActronAir split at an Airds food shop showing PC01. What the code means, how we test it, and everything else we found on the roof.
Actron PC01 Fault: What It Means, and a Real Airds Job
What An Actron PC01 Fault Means
On this ActronAir split, PC01 is a voltage protection fault. The outdoor unit has shut itself down because the voltage on its circuit board is out of range. The indoor unit usually keeps talking to the outdoor, but the outdoor fan and compressor won't start, and the code comes up after a couple of minutes.
The supply might be the problem, or the board might have failed. Before anyone fits a new board, you need to know the compressor didn't cause it, or the new board can fail the moment it's powered up.
How we diagnose a PC01, step by step
- Measure the supply voltage at the outdoor unit to rule the power in or out.
- Confirm the indoor and outdoor units are communicating.
- Check the outdoor fan and compressor are getting a start signal.
- Test the compressor windings for balance. Healthy windings read the same across all three.
- Inspect the board for burn damage and the unit for loose connections or missing parts.
- Recommend an insulation test on the compressor before a new board goes in.
- Look at the install itself: clearances, isolator, tie-downs. Those are often why a board failed in the first place.
What not to do
- Don't keep resetting it. If the board's sensing a voltage problem, forcing it to restart won't help.
- Don't fit a new board without testing the compressor first.
- Don't work on a rooftop unit with no isolator. One should always be fitted so the unit can be made safe.
More codes in our Actron error codes guide, and see commercial air conditioning repairs.
The Job
- Suburb: Airds
- Job: Commercial diagnostic, error code
- System: ActronAir 7.2kW split
- Price: $250+GST diagnostic fee
A local food shop's split system was showing PC01 and had stopped working.
What We Found
The outdoor board had failed. Before blaming the board, we tested the compressor windings, and they were balanced and healthy.
The rest of the install told a story. The last person to work on it had left screws out and cables loose. The indoor unit was mounted less than 100 mm from the ceiling, which chokes its airflow. There was no outdoor isolator, and the tie-down straps had been removed, leaving holes in the roof.
And partway through the test, a plover on the roof started swooping and attacking. With no isolator at the unit, it caused the circuit to short and trip, which cut power to the site. Work on the outdoor unit was put on hold until the plover was sorted. All part of the job.
The readings
- Supply voltage: 249.7V
- Compressor windings: 1.2 to 1.3 ohms, balanced
What We Did And Recommended
Our quote covered a new board after an insulation test on the compressor, fitting an outdoor isolator, securing the unit properly, sealing the roof, and cleaning the indoor unit and filter. We also priced a replacement so the owner could compare.
For a food business, a working system and a safe install both matter. We'd rather fix it properly once.
More on Actron error codes, commercial air conditioning repairs, and our Campbelltown air conditioning page, which covers Airds.
FAQ
Common Questions
On this system it’s a voltage protection fault. The outdoor unit shuts down because the voltage on its circuit board is out of range. The cause can be the supply or a failed board.
If the compressor caused the board to fail, a new board can be damaged as soon as it’s powered up. An insulation test on the compressor first protects the new part.
Yes. An isolation switch at the outdoor unit lets it be switched off safely for service. This one didn’t have one, so we recommended fitting it.
Our diagnostic is $250+GST. We test it, write up exactly what we found, and price the repair, plus a replacement if the system’s older, so you can compare.
Get A Report Like This For Your System
Every Standard Service ($250+GST, $110+GST for each extra unit) comes with a written report like this one, with readings and photos, emailed to you the same day. Diagnostics are $250+GST and come with a written report too.
Give us a call on (02) 9820 4500 or book online. Our own crew, not subbies. NSW contractor licence 273312C, ARCtick AU13058. Servicing Sydney since 1991.